Sunday 15 March 2020

DAIKIN inverter AC error codes - FTXS30LVJU, FTXS36LVJU, RKS30LVJU, RKS36LVJU


Indoor Unit
FTXS30LVJU, FTXS36LVJU
Outdoor Unit
RKS30LVJU, RKS36LVJU
U0
Refrigerant Shortage
Refrigerant shortage detection I:  Refrigerant shortage is detected by checking the input current value and the compressor running frequency. If the refrigerant is short, the input current is lower than the normal value.
Refrigerant shortage detection II:  Refrigerant shortage is detected by checking the discharge pipe temperature and the opening of the electronic expansion valve. If the refrigerant is short, the discharge pipe temperature tends to rise.
Refrigerant shortage detection III:  Refrigerant shortage is detected by checking the difference between suction and discharge temperature.
Supposed Causes
 Disconnection of the discharge pipe thermostat, indoor or outdoor heat exchanger  thermostat, room or outdoor temperature thermistor
 Closed stop valve
 Refrigerant shortage (refrigerant leakage)
 Poor compression performance of compressor
 Defective electronic expansion valve.
U2
Low-voltage Detection or Over-voltage Detection
Indoor Unit
The zero-cross detection of the power supply is evaluated by the indoor unit PCB.
Outdoor Unit
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Supposed Causes
 Supply voltage is not as specified.
 Defective DC voltage detection circuit
 Defective over-voltage detection circuit
 Defective PAM control part
 Disconnection of compressor harness
 Noise
 Momentary fall of voltage
 Momentary power failure
 Defective indoor unit PCB
U4
Signal Transmission Error (between Indoor Unit and Outdoor Unit)
The data received from the outdoor unit in indoor unit-outdoor unit signal transmission is checked whether it is normal.
The data sent from the outdoor unit cannot be received normally, or the content of the data is abnormal.
Supposed Causes
Wiring error
Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
Defective outdoor unit PCB
Defective indoor unit PCB
Disturbed power supply waveform.
U7
Signal Transmission Error on Outdoor Unit PCB
Communication error between microcomputer mounted on the main microcomputer and PM1.
The abnormality is determined when the data sent from the PM1 can not be received for 9
seconds.
 The error counter is reset when the data from the PM1 can be successfully received.
 Supposed Causes
Defective outdoor unit PCB.
UA
Unspecified Voltage
The supply power is detected for its requirements (different from pair type and multi type) by the
indoor / outdoor transmission signal.
The pair type and multi type are interconnected.
Supposed Causes
 Wrong models interconnected
 Wrong wiring of connecting wires
 Wrong indoor unit PCB or outdoor unit PCB mounted
 Defective indoor unit PCB
 Defective outdoor unit PCB
E1
Outdoor Unit PCB Abnormality
 The system checks if the microprocessor is working in order.
 The system checks if the zero-cross signal comes in properly.
 The microprocessor program runs out of control.
 The zero-cross signal is not detected.
Supposed Causes
 Defective outdoor unit PCB
 Broken harness between PCBs
 Noise
 Momentary fall of voltage
 Momentary power failure, etc.
E5
OL Activation
A compressor overload is detected through compressor OL.
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 60 minutes without any other error.
* The operating temperature condition is not specified.
Supposed Causes
 Defective discharge pipe thermistor
 Defective electronic expansion valve or coil
 Defective FourWay valve or coil
 Defective outdoor unit PCB
 Refrigerant shortage
 Water mixed in refrigerant
 Defective stop valve.
E6
Compressor Lock
A compressor lock is detected by checking the compressor running condition through the position detection circuit.
09/12 class
 Operation stops due to over current.
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 11 minutes without any other error
15/18/24/30/36 class
 A compressor lock is detected by the current waveform generated when applying high frequency voltage to the motor.
 If the error repeats, the system is shut down
 Reset condition: Continuous run for about 5 minutes without any other error.
Supposed Causes
 Compressor locked
Compressor harness disconnected
E7
DC Fan Lock
 An error is determined with the high-voltage fan motor rotation speed detected by the Hall  IC.
 The fan does not start in 15 ~ 30 seconds (depending on the model) even when the fan  motor is running.
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 11 minutes (09/12 class) or 5 minutes (15/18/24/30/ 36 class) without any other error.
Supposed Causes
 Foreign matter stuck in the fan
 Defective fan motor
 Defective outdoor unit PCB
E8
Input Over current Detection
An input overcurrent is detected by checking the input current value with the compressor running.
 The current exceeds about 9.25 ~ 20 A for 2.5 seconds with the compressor running.
(The upper limit of the current decreases when the outdoor temperature exceeds a certain level.)
Supposed Causes
 Outdoor temperature is out of operation range.
 Defective compressor
 Defective power module
 Defective outdoor unit PCB
 Short circuit
EA
FourWay Valve Abnormality
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
function within their normal ranges in each operation mode.
A following condition continues over 1 ~ 10 minutes after operating for 5 ~ 10 minutes.
 Cooling / Dry
(room thermistor temp. – indoor heat exchanger temp.) < –5°C (–9°F)
 Heating
(indoor heat exchanger temp. – room thermistor temp.) < –5°C (–9°F)
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 60 minutes without any other error.
Supposed Causes
 Disconnection of fourway valve coil
 Defective fourway valve, coil, or harness
 Defective outdoor unit PCB
 Defective thermistor
 Refrigerant shortage
 Water mixed in refrigerant
 Defective stop valve
F3
Discharge Pipe Temperature Control
An error is determined with the temperature detected by the discharge pipe thermistor.
Supposed Causes
 Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
 Defective electronic expansion valve or coil
 Refrigerant shortage
 Defective fourway valve
 Water mixed in refrigerant
 Defective stop valve
 Defective outdoor unit PCB
F6
High Pressure Control in Cooling
High-pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if the
temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Supposed Causes
 The installation space is not large enough.
 Dirty outdoor heat exchanger
 Defective outdoor fan motor
 Defective stop valve
 Defective electronic expansion valve or coil
 Defective outdoor heat exchanger thermistor
 Defective outdoor unit PCB
H0
Compressor System Sensor Abnormality
 The system checks the DC current before the compressor starts.
 The DC current before compressor start-up is out of the range 0.5 ~ 4.5 V (sensor output
 converted to voltage value)
 The DC voltage before compressor start-up is below 50 V.
Supposed Causes
 Broken or disconnected harness
 Defective outdoor unit PCB
H0
 The system checks the supply voltage and the DC voltage before the compressor starts.
 The system checks the compressor current right after the compressor starts.
 The supply voltage and the DC voltage is obviously low or high.
 The compressor current does not run when the compressor starts.
Supposed Causes
 Disconnection of reactor
 Disconnection of compressor harness
 Defective outdoor unit PCB
 Defective compressor
H6
Position Sensor Abnormality
A compressor start-up failure is detected by checking the compressor running condition through the position detection circuit.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes (09/12 class) or 5 minutes (15/18/24/30/ 36 class) without any other error
Supposed Causes
 Disconnection of the compressor relay cable
 Defective compressor
 Defective outdoor unit PCB
 Start-up failure caused by the closed stop valve
 Input voltage is outside the specified range.
H8
DC Voltage / Current Sensor Abnormality
DC voltage or DC current sensor abnormality is identified based on the compressor running frequency and the input current.
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 60 minutes without any other error
Supposed Causes
 Defective outdoor unit PCB
H8
CT or Related Abnormality
A CT or related error is detected by checking the compressor running frequency and CT-detected input current.
Supposed Causes
 Defective power module
 Broken or disconnected wiring
 Defective reactor
 Defective outdoor unit PCB
H9,J3,J6,P4
Thermistor or Related Abnormality (Outdoor Unit)
This fault is identified based on the thermistor input voltage to the microcomputer. A thermistor fault is identified based on the temperature sensed by each thermistor.
Supposed Causes
 Disconnection of the connector for the thermistor
 Defective thermistor corresponding to the error code
 Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger thermistor in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
L3
Electrical Box Temperature Rise
 An electrical box temperature rise is detected by checking the radiation fin thermistor with the compressor off.
Supposed Causes
 Defective outdoor fan motor
 Short circuit
 Defective radiation fin thermistor
 Disconnection of connector
 Defective outdoor unit PCB
L4
Radiation Fin Temperature Rise
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the compressor on.
Supposed Causes
 Defective outdoor fan motor
 Short circuit
 Defective radiation fin thermistor
 Disconnection of connector
 Defective outdoor unit PCB
 Silicon grease is not applied properly on the radiation fin after replacing the outdoor unit PCB.
L5
Output Overcurrent Detection
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Supposed Causes
 Poor installation condition
 Closed stop valve
 Defective power module
 Wrong internal wiring
 Abnormal power supply voltage
 Defective outdoor unit PCB
 Defective compressor

LG 52LG50FD, 52LG50FD-SA-Service adjustments-service mode entry-white balance adjustment-ADC component 1 RGB adjustment and more

  These adjustments are similar to 42LB7DF Because this is not a hot chassis, it is not necessary to use an isolation transformer. However...